Term · Gas fire suppression
EN 15004
Knowledge Base
Related products and services
Gas fire suppression
Related reading
- How is the FM-200 quantity calculated?The quantity is calculated from the net protected volume, the lowest design ambient temperature and the design concentration defined in the standard (TS EN 15004 or NFPA 2001) for the fire class. Raised-floor voids and ceiling voids are treated as separate volumes, and the result is verified with a hydraulic calculation of pipes and nozzles.
- How does an FM-200 gas suppression system work? Components and design stepsFM-200 (HFC-227ea) systems discharge a clean extinguishing agent into the protected volume within about 10 seconds of fire detection; the agent extinguishes mainly by absorbing heat from the flame and leaves no residue. A system consists of detection, a control panel, agent cylinders, piping and nozzles, and is designed around the integrity of the protected volume.
- FM-200 (HFC-227ea)FM-200 is the trade name of heptafluoropropane (HFC-227ea). This colourless, odourless and non-conductive clean agent extinguishes fire mainly by absorbing heat from the flame and leaves no residue.
- Does FM-200 damage equipment or data?No. FM-200 is electrically non-conductive and leaves no residue; equipment does not get wet and needs no cleaning. That is why it is preferred in rooms with energized electronic equipment. Fast extinguishing also limits the damage the fire itself can cause.